Application Note for External RCD Selection 


Solis inverters have a residual current monitoring unit (RCMU) integrated inside which complies with the requirements of IEC 62109-1 and IEC 62109-2.

In case of a sudden change in residual current, Solis inverters will disconnect from the grid within the following time specified in the table and show alarm code accordingly.

Note: Local requirements trump IEC requirements, so if there are more stricter local requirements, then you as an installer need to follow those

 

 

Residual Current Sudden Change

Max Time to Disconnect From Grid

Alarm Code

 

30mA

 

0.3s

 

Ileak-PRO 01

 

60mA

 

0.15s

 

Ileak-PRO 02

 

150mA

 

0.04s

 

Ileak-PRO 03

 

 

In case of continuous residual current, Solis inverters will disconnect from the grid within 0.3s and show the alarm code “Ileak-PRO04”, if the continuous residual current exceeds the values in the following table.

 

 

Inverters with continuous output power rating ≤ 30kVA

Max 300mA

Inverters with continuous output power rating > 30kVA

 

Max 10mA per kVA

 

 

External RCD may be required to be installed in some countries. Since Solis inverters by design is not able to feed in DC residual current to grid, Solis recommends installing external Type A RCD with Solis inverters and the recommended ratings are listed below:

 

 

Inverter model

Recommended External Type A RCD Rating

Max Continuous Residual Current in IEC 62109

S6-GR1P(0.7-3.6)K-M

100mA

300mA

S6-GR1P(2.5-6)K

100mA

300mA

S6-GR1P(2.5-6)K-S

100mA

300mA


 

Solis-1P(7-8)K-5G

100mA

300mA

S5-GR1P(7-10)K

100mA

300mA

S5-GR3P(3-10)K

100mA

300mA

S5-GR3P(12-20)K

300mA

300mA

S5-GC25K

300mA

300mA

S5-GC30K

300mA

330mA

S5-GC33K

300mA

363mA

S5-GC36K

300mA

396mA

S5-GC40K

300mA

440mA

S5-GC50K

400mA

550mA

S5-GC60K

500mA

660mA

S5-GC80K/Solis-80K-5G/ Solis- 80K-5G-PRO

700mA

880mA

S5-GC100K/Solis-100K-5G/ Solis- 100K-5G-PRO

900mA

1100mA

S5-GC110K/Solis-110K-5G/ Solis- 110K-5G-PRO

1000mA

1210mA

S6-GC125K

1A

1250mA

S6-GC3P150K07-NV-ND

1A or 1.5A

1500mA

RAI-3K-48ES-5G

100mA

300mA

RHI-3P(3-10)K-5G

100mA

300mA

S5-EH1P(3-6)K-L

100mA

300mA

S6-EH1P(3-6)K-L

100mA

300mA

S6-EH1P(3-8)K-PRO/PLUS

100mA

300mA

S6-EH3P(3-10)K-H

100mA

300mA

S6-EH3P12K-H

300mA

300mA

S6-EH3P15K-H

300mA

300mA

S6-EH3P20K-H

300mA

300mA


 

S6-EH3P29.9K-H

300mA

330mA

S6-EH3P30K-H

300mA

330mA

S6-EH3P40K-H

300mA

440mA

S6-EH3P50K-H

400mA

550mA

RAI-3K-48ES-5G

100mA

300mA

RHI-3P(3-10)K-5G

100mA

300mA

 

Note: Recommendations also apply to other derived models with suffixes such as -4G, -5G, -LV, -HV, etc. with the same power rating.