Solis inverters have a residual current monitoring unit (RCMU) integrated inside which complies with the requirements of IEC 62109-1 and IEC 62109-2.  


In case of a sudden change in residual current, Solis inverters will disconnect from the grid within the following time specified in the table and show alarm code accordingly. 


Residual Current Sudden Change 

Max Time to Disconnect From Grid 

Alarm Code 

30mA 

0.3s 

Ileak-PRO 01 

60mA 

0.15s 

Ileak-PRO 02 

150mA 

0.04s 

Ileak-PRO 03 


In case of continuous residual current, Solis inverters will disconnect from the grid within 0.3s and show the alarm code “Ileak-PRO04”, if the continuous residual current exceeds the values in the following table. 


Inverters with continuous output power rating ≤ 30kVA 

Max 300mA 

Inverters with continuous output power rating  30kVA 

Max 10mA per kVA 


External RCD may be required to be installed in some countries. Since Solis inverters by design is not able to feed in DC residual current to grid, Solis recommends installing external Type A RCD with Solis inverters and the recommended ratings are listed below: 


Inverter model 

Recommended External Type A RCD Rating 

Max Continuous Residual Current in IEC 62109 

S6-GR1P(0.7-3.6)K-M 

100mA 

300mA 

S6-GR1P(2.5-6)K 

100mA 

300mA 

S6-GR1P(2.5-6)K-S 

100mA 

300mA 

Solis-1P(7-8)K-5G 

100mA 

300mA 

S5-GR1P(7-10)K 

100mA 

300mA 

S5-GR3P(3-10)K 

100mA 

300mA 

S5-GR3P(12-20)K 

300mA 

300mA 

S5-GC25K 

300mA 

300mA 

S5-GC30K 

300mA 

330mA 

S5-GC33K 

300mA 

363mA 

S5-GC36K 

300mA 

396mA 

S5-GC40K 

300mA 

440mA 

S5-GC50K 

400mA 

550mA 

S5-GC60K 

500mA 

660mA 

S5-GC80K/Solis-80K-5G/ Solis-80K-5G-PRO 

700mA 

880mA 

S5-GC100K/Solis-100K-5G/ Solis-100K-5G-PRO 

900mA 

1100mA 

S5-GC110K/Solis-110K-5G/ Solis-110K-5G-PRO 

1000mA 

1210mA 

S5-EH1P(3-6)K-L 

100mA 

300mA 

S6-EH1P(3-6)K-L 

100mA 

300mA 

S6-EH1P(3-8)K-PRO/PLUS 

100mA 

300mA 

S6-EH3P(3-10)K-H 

100mA 

300mA 

RAI-3K-48ES-5G 

100mA 

300mA 

RHI-3P(3-10)K-5G 

100mA 

300mA 


Note: Recommendations also apply to other derived models with suffixes such as -4G, -5G, -LV, -HV, etc. with the same power rating. 

 

 


 LinkedIn Facebook Instagram YouTube Twitter







Was this article helpful?

That’s Great!

Thank you for your feedback

Sorry! We couldn't be helpful

Thank you for your feedback

Let us know how can we improve this article!

Select at least one of the reasons
CAPTCHA verification is required.

Feedback sent

We appreciate your effort and will try to fix the article