How to configure a DTSD1352 Acrel Meter for connection in a 3Phase 3 wire - LV network

Modified on Fri, 20 Oct, 2023 at 12:15 PM

Step 1: On meter working interface, press’ SET ‘key( first from the left ) to enter Setting interface


Step 2: In Settings interface, press ‘Enter’ key

Use in the password on the password input interface:

UI/▲ key (second from the left) is to adjust the figure position, E/▼ (third from the left) is to

adjust the value. After entering the password, press the enter key (fourth from the left) to enter

the setting configuration interface (if no password has been set before, use initial password which

is 0001)

Step 3:

Enter ‘SYS’ interface by pressing on UI/▲ key (second from left) and E/▼ (third from the left)

then press Enter to access in configuration interface

Step 4:

Press on the UI/▲ key (second from the left) and E/▼ (the third from the left) to adjust to the PL

interface (as shown in the picture below), and press the enter key (the fourth from the left) to display

the current line system (example: for a a three-phase three-wire select 3P3L) adjust

the wiring system by pressing the UI/▲ key and E/▼ key.


Step 5:

After making these changes, press the Enter key to exit from the setting interface. At this time,

press the SET key twice (the first from the left) to jump to the interface and go to the SAVE (save)

interface.

Step 6

Choose ‘Yes’ to save the change, and configuration is completed.

Note:

in this configuration, the connection diagram of the DTSD1352 Acrel Meter with CT should be as below