Adjust the CT ratio of an Acrel DTSD 1352 meter

Modified on Thu, 14 Oct, 2021 at 11:35 AM

The default value normally set on a Acrel DTSD 1352  meter is 30, as the CTs delivered with this meter are Acrel AKH-.66 K24 - 150A:5A

If you choose to use different CT clamps, you can change on meter's display by following the below EXACT steps.



Press SET button to enter the Main Menu and get in “PASS” interface, and then press Enter  to show

“0000”, and enter the code 0008-> Press Enter and navigate to In.->Transformer settings-> CT

 

Adjust Ct ratio to correct value -> press Enter-> Press Set x 2 times-> press Enter to Save-> Press Down to change to Yes-> Press Enter to save