Hybrid Backup Port - Alarm Information & Operational Details


Purpose

This article explains how the Hybrid Backup Port behaves when inverter alarms occur and clarifies the interaction between inverter faults and the Backup Port / Bypass function for the 30-125K Hybrid range. The information is based on the alarm operation spreadsheet provided.

Full Excel is attached


Important Notes

  1. This document contains two operational views/tabs in the original reference material.
  2. These alarm behaviours are only applicable to:
    • S6-EH3P(29.9-60)K-H(21A), including previous versions.
    • S6-EH3P(80-125)K10-NV-YD-H.

What Alarms Will Kick Off the Backup Port?

Principle

When an alarm results in the inverter being shut down due to a malfunction, the Backup Port is also disabled. In the alarm list, these faults are marked with"Y" under"Is the machine down due to a malfunction?".


Bypass Function Behaviour

When Bypass is Enabled

The Bypass function allows the load to be supplied via the bypass path when inverter operation is unavailable.

Alarms That Will Affect Bypass

Any fault that causes an inverter shutdown (marked Y) should be considered capable of impacting normal inverter-backed operation and may cause transfer to or restriction of backup functionality, depending on system operating mode and installation design.

Alarms That Will Not Affect Bypass

Alarms marked N are warning or non-shutdown conditions. These alarms do not stop inverter operation and therefore do not normally prevent the Bypass function from remaining available.


Quick Reference

Alarm TypeMachine ShutdownBackup Port Impact
Faults marked YYesBackup Port disabled / affected
Faults marked NNoBackup Port remains operational

Source alarm classification based on the"Is the machine down due to a malfunction?" field in the 30-125K Hybrid alarm operation document.


Summary:
For the 30-125K Hybrid platforms listed above, the simplest rule is: If the alarm is marked "Y" in the alarm table, the inverter shuts down and the Backup Port is affected. If the alarm is marked "N", the inverter remains operational and the Backup Port is not affected by that alarm condition.



Examples of Faults That Disable Backup Port Operation (alarms marked with "Y")

PV / DC Side Protection

  • OV-DC01 to OV-DC10 (DC input overvoltage)
  • OV-DC01-I to OV-DC10-I (DC overcurrent)
  • Reve-DC (DC reverse polarity)
  • OV-BUS (DC bus overvoltage)
  • UNB-BUS (DC bus voltage imbalance)
  • UN-BUS (DC bus voltage detection abnormality)
  • DC-INTF (DC hardware overcurrent)

Backup and AC Hardware Protection

  • UN-Vbackup (Offline undervoltage fault)
  • OV-Iac-H (AC hardware overcurrent)
  • OV-GI (AC effective value overcurrent)
  • OV-Vbackup (Inverter overvoltage fault)
  • Bkup-NtoPE-Err (Backup neutral-ground fault)
  • OV-Panel-I (Switchboard overcurrent)

Battery Related Faults

  • OV-Ibatt-H
  • Batt-Overload
  • OV-Vbatt
  • OV-Vbatt-H
  • Batt-ON-Fail

Temperature, Isolation and Safety Protection

  • OV-TEM (Module overheating)
  • PV-ISO-PRO01 / 02
  • ILeak-PRO01 to 04
  • ILeak-Check
  • AFCI-Check
  • ARC-Fault

Hardware / Communication Faults Causing Shutdown

  • DSP-B-Fault
  • DSP-SelfCheck
  • DSP-Match-Err
  • DSP-Comm-Fail
  • MasterSyncLose
  • MasterSyncErr
  • Addr-Conflict
  • HeartbeatLose
  • DCanErr
  • MulMasterErr
  • ModeConflict
  • MasterFailure
  • 3P_CreateFail
  • Startup-Fail
  • Par-Mdl-Mismatch
  • Par.Bkup-Open



Examples of Alarma That Do NOT Disable Backup Port Operation (alarms marked with "N")

Grid Related Events

  • OV-GV
  • UV-GV
  • OV-GF
  • UN-GF
  • NO-Grid
  • GF-GLU
  • Uac-Unstable
  • Phase-Fault

Battery Warnings

  • NO-Battery
  • NO-Battery2
  • UN-Vbatt
  • UN-Vbatt2
  • OV-Vbatt2
  • Batt-Comm-Fail
  • Alarm1-BMS
  • Alarm2-BMS

Monitoring / Communication Warnings

  • Meter-Comm-Fail
  • Batt485-Err
  • G100-ComFail
  • G100-CTFault
  • PVInv-ComFail
  • Meter2-Fail
  • SPH-Comm-Fail
  • SHub-DSP-CommErr

Miscellaneous Warnings

  • FanAlarm-Int.
  • FanAlarm-Ext.
  • BK-CB-Ovload
  • Surge-Alarm
  • LowBattery
  • Gen-Start-Fail
  • Gen-Stop-Fail
  • ACCoupling-Stop
  • ACCoupling-Lock 