For limiting the export on the inverter, depending on the exact model of the inverter, customers can use use the internal EPM (Export Power Limit) function and have a meter communicating with the inverter (see attached meter compatibility list).
For limiting the export to the grid
Step 1
Determine if meter connection is Meter in Grid or Meter in Load, and select appropriate Mode Select.
Advanced Settings (password 0010)->Internal EPM -> Mode select
Step 2
Set backflow power value to desired maximum value to be exported.
Advanced Settings ->internal EPM -> Backflow Power
Step 3
Enable Failsafe option
Advanced Settings ->internal EPM -> Failsafe
This setting is used to give out an alarm (stop inverter generation as well) when the Meter
connection is lost during operation.
It can prevent potential backflow power into the grid when the system loses control.