EPM 5G-Plus + RHI-3P(3-10)K-HVES-5G
Parallel Operation
Discover the untapped potential of your solar energy system with the parallel operation option offered by Solis RHI Three-Phase Inverters.
In this article, we explore how this feature allows users to maximize energy production effortlessly.
For any additional assistance, Solis Support team is readily available to assist you and to ensure a seamless solar experience.
Let's delve into the world of parallel operation and empower users to harness the full power of the sun with confidence in reliable support.
Note:
Currently, this scenario is not being accurately displayed on SolisCloud.
Our dedicated SolisCloud Support team is actively addressing the issue to ensure that this scenario will be correctly displayed on our SolisCloud Platform.
Index:
- Applicable Devices
- Requirements
- Connection Diagrams
- EPM 5G-Plus – Internal Data Logger Disconnection
- Devices configuration
Applicable Devices:
- Solis-EPM3-5G-Plus
- RHI-3P(3-10)K-HVES-5G
- Solis Three-Phase PV Inverters
Requirements:
For connecting in parallel Solis Hybrid Inverters RHI-3P(3-10)K-HVES-5G with Solis Three-Phase PV Inverters, some items are compulsory to be added into the system:
- 1 pc. - Solis-EPM 5G-Plus
- 2 pcs. - S3-GPRS/WiFi-ST Data Loggers
- 3 pcs. - CTs dimensioned with the primary according to site capacity and having 5A in the secondary
- A stable Internet Connection
https://www.solisinverters.com/global/downloadcenter.html
Schedule a call/meeting with Solis Service, at least 4 days before commissioning, providing them all the information of the system (system components, configuration, missing parts, etc.).
Notes:
1. The firmware version of all devices must be upgraded to the latest tested version.
2. The EPM-Plus HMI firmware version required for this type of configuration is 1E.
3. The PV Inverters need to be upgraded to a special version only if the site requires Export Limitation function.
Connection Diagrams:
Electrical Diagram
ModBus RTU - RS485 Communication between the inverters and EPM
Yellow chain Positive (+)
Blue chain Negative (-)
EPM-Plus – Internal Data Logger Disconnection
To enable the EPM update via the S3-WiFi-ST Data Logger, it is necessary to disable the internal Logger of the device.
There are two ways to do this:
Note:
Before proceeding with this step please check with Support Team which is the model of the EPM-Plus internal Data Logger. If the internal Data Logger is already an S2-WiFi-Logger, the step below can be skipped.
1. Disabling by disconnecting the internal wiring (recommended)
You need to open the EPM enclosure and disconnect the connections, as shown in the image below:
Note: After internal Data Logger disconnection, the external S3-GPRS/WiFi-ST Logger can be twisted on the EPM.
2. Disabling from software
Step 1: Turn ON the EPM device.
Step 2: Turn ON the WiFi on your mobile phone, search for the Logger’s hotspot displayed as AP_xxxxxxxxx and connect to it.
Step 3:
- Open a browser on your mobile phone (e.g. Safari, Chrome)
- In the search bar of the browser type: 10.10.100.254 and access
- Click on “Advanced”--> “Work Mode”
- Change the Working mode to “Transparency”
- Press “Save”
Wait for about 10 seconds, then the "Restart" option will appear, click "Restart".
Step 4:
During WiFi Restart, the signal will be disconnected from the mobile phone.
Try to refresh the WiFi list until you find again AP_xxxxxxxxx and reconnect.
Doble check in “Working Mode", to be sure that "Transparency" mode is active (VERY IMPORTANT).
DEVICES CONFIGURATION
1. EPM3-5G-Plus
1.1 Transmit ON/OFF
Path: Advanced Settings à Password: 0010 à Transmit ON/OFF
Set to: OFF
1.2. Address
Set the address: 01
Path: Settings à Set Address à 01
Note: If the S3-GPRS/WiFi-ST Data Logger is not properly detected, it is recommended to disconnect the internal wiring as indicated above.
1.3. Inverter Qty Set
Set the maximum number of slave addresses that will be allocated to the inverters.
Path: Advanced setting → Password: 0010 à Inverter Qty. Set à Set INV Num: Max number of slave address among all inverters.
Example: 3 hybrid inverters in parallel with slave address 02, 04, 06. Set Inverter Qty. Set to “06”
1.4. Set Capacity
Set to: Rated Power of all inverters under the EPM.
Path: Advanced settings à Password: 0010 à Set Capacity à Adding up the “Rated Power” of all inverters under the EPM
1.5. Set Meter CT
Set to: CT ratio of the external CTs
Path: Advanced setting à Password: 0010 à Set Meter CT à CT ratio of the external CT
Example: If 100:5A CT are used, set the CT ratio as 20:1
1.6. Backflow Power
Set the allowed backflow power.
Path: Advanced settings à Password: 0010 à Backflow Power à Set Power à Allowed backflow power.
1.7. Backflow Work Mode
Set to: 01
Path: Advanced settings à Password: 0010 à Backflow Work Mode à01
1.8. Inverter type
If there is at least one Hybrid Inverter, select “Hybrid Inverter”.
If all connected inverters are grid tied inverters, choose “PV inverter”
Path: Advanced settings à Password: 0010 à Inverter Type à Hybrid Inverter
1.9. FailSafe ON/OFF
Set to: Run
Path: Advanced settings à Password: 0010 à FailSafe ON/OFF à FailSafe: RUN
1.10. Set the PT ratio
Set the PT ratio for the EPM PT: 1:1
Path: Advanced Settings à Password: 0010 à Set Meter PT à Set PT Para: 0001:1
2. Solis Three-Phase PV Inverters
2.1 Set Address
Set to: Odd Number (01, 03, 05, etc.). Set a different address on each inverter.
Path: Settings à Set Address à Odd number
2.2 Internal EPM Set
Set to: OFF
Path: Advanced Settings à Password: 0010 à Internal EPM Set à Mode Select: OFF
2.3 External EPM Set
Set to: ON
Path: Advanced settings à Password: 0010 à External EPM set à 5G-EPM à Fail Safe Set: ON
Note:
In case the Export Limitation is a requirement of the site, for the EPM to be able to control and limit the string inverters as well, it is necessary to upgrade the HMI to a specific firmware released for that model.
This operation can be performed by the Service Team remotely, once the inverters have been connected to the WiFi using the second Data Logger and before connecting it to EPM.
If it is not necessary to control the export, the special firmware upgrade for PV inverters is not required.
3.Hybrid inverters
3.1 Set Address
Set to: Even Number (02, 04, 06, etc.). Set a different address on each inverter.
Path: Settings à Set address à Even number
3.2 Meter Select
Set to: No Meter
Path: Advanced settings à Password: 0010 à Storage Energy Set à Meter Select à No meter
3.3 Int EPM Set
Set to: OFF
Path: Advanced settings à Password: 0010 à Int EPM Set à EPM ON/OFF→OFF
3.4 Ext EPM Set
Set to: ON
Path: Advanced settings à Password: 0010 à Ext EPM Set à Ext EPM ON/OFF à ON à Fail Safe ON/OFF→ON
3.5 Self Use Mode
Set to: ON and Allow grid charging
Path: Advanced settings à Password: 0010 à Stg Mode Select à Self use à ON à Charging from grid à Allow
We hope that this article has provided valuable insights.
If you have any further questions or concerns, please do not hesitate to reach out to your local Solis Support team.